Article Open Access1 January 2020

Comparative analysis of cascade refrigeration system based on energy and exergy using different refr

Order Reprints Cite Share

Vipin KUMAR1

1Vidya College of Engineering

Journal of Thermal Engineering 2020, Vol. 6, Issue 1, pp. 106-116; doi.org/10.18186/thermal.671652

Download PDF View DOI record

Abstract

In this study a comparative analysis on the basis of energy and exergy of cascade refrigeration system using different refrigerant pair, R13 for low temperature cycle (LTC) and R134a, R290 and R717 for high temperature cycle (HTC) has been done by mathematical simulation using Engineering Equation Solver (EES-V9.224-3D). The analysis of cascade refrigeration system has been carried out at different operating condition and result has been compared with effect of various operating parameters. The range of evaporator temperature of LTC is taken from -53oC to -70oC, which represents the most common operating condition in commercial applications. The range of condenser temperature of LTC is from -11oC to -2oC and evaporator temperature of HTC from -19oC to -10oC.Results show that the refrigerant pair R13-R717 is the best suitable refrigerant pair for proposed cascade refrigeration system in comparison to other used refrigerant pairs and R717 can be a interesting alternative refrigerant to R134a and R290 for high temperature cycle of cascade refrigeration system in commercial applications.

Keywords: Cascade Refrigeration System; High Temperature Circuit; Low Temperature Circuit; COP

Introduction

Today the demand of energy is increasing day by day in the field of thermal comfort. And to get low temperature, cascade refrigeration system is being widely used in many industrial applications. Cascade refrigeration system is combination of more than one refrigeration systems that works independently. The low temperature cycle provides the desired refrigeration effect at a relatively low temperature. The condenser in the low temperature cycle is thermally coupled to the evaporator in the high temperature cycle. Thus, the evaporator in the high temperature cycle only serves to extract the heat released by the condenser in the low temperature cycle. Then this heat is rejected to the ambient air or water stream in the condenser of the high temperature cycle. A cascade refrigeration system can operate with a low evaporating temperature, lower compression ratio and high compressor volumetric efficiency in comparison with a single-stage refrigeration system. Refrigerant in Low temperature cycle enters the compressor as a saturated vapour, after extracting the heat from the space to be cooled and as it gets compressed, the temperature and pressure increases. After exiting from the compressor, the refrigerant passes through the cascade condenser where heat is transferred to the evaporator of the high temperature cycle. Finally, the refrigerant enters the throttling valve, gets expanded and the cycle repeats itself.

Literature Review

In many industrial and medical applications, we need temperature below -40°C for that, a single stage vapour compression system can’t be used [1]. Among all the refrigerants, selection of refrigerant is very important. The selected refrigerant must have low global warming potential (GWP) and zero ozone depletion potential (ODP). There are some natural refrigerants like NH3 and CO2, which are being widely used in many industrial refrigeration systems [1, 4, 6]. Advance exergy analysis gives the more accurate results which provide the recommendations for refrigeration system improvement. Advanced exergy performance analysis gives better results in comparison to conventional energy analysis [15]. Ehsan G et. al.[1] evaluated a cascade refrigeration system based on advanced exergy analysis and suggested that throttling valve, compressor and cascade heat exchanger needs more improvements. Umesh C.R. [2] evaluated the performance of cascade refrigeration system with refrigerant pair R404a-R23. S Ponsankar et. al.[6] This paper was recommended for publication in revised form by Regional Editor Erdal Çetkin 1 Vidya College of Engineering, India 2 Jamia Millia Islamia, New Delhi, India *E-mail address: ervipinkumar09@gmail.com Orcid id: 0000-0003-4530-019X, 0000-0002-9637-6859 Manuscript Received 06 March 2019, Accepted 23 July 2019

Journal of Thermal Engineering, Technical Note, Vol. 6, No. 1, pp. 106-116, January, 2020 performed the irreversibility analysis of cascade refrigeration system with different refrigerant pair and concluded that increment in evaporator temperature will increase COP and decrease the system irreversibility. Refrigerant pair R134a-R23 has minimum irreversibility. Nasruddini et. al. [7] performed the thermodynamic optimization of cascade refrigeration system with environment friendly refrigerant pair and finds the optimum exergy efficiency and its relation with cost. Sertac S.S. et.al. [13] has analyzed exergy for a two stage cascade refrigeration system with flash tank using R600, R290, R152a, and R141b as refrigerants. He has calculated the exergy value of all the components using EES and concluded that the flash tank has minimum exergy loss and with R141a refrigerant, the total irreversibility loss is minimum. Yasin U. A. et. al.[15] analyzed a cascade refrigeration system based on exergetic performance coefficient and finds that refrigerant couple R23-R717 gives the best result. S.M. H. mohammadi et. al.[17] has analyzed a cascade refrigeration system consisting of a compression and an absorption chillers. He has shown that such a system would increase the efficiency of the energy usage up to 50% compared to a traditional single stage air conditioning system. Bayram K et. al.[19] worked on exergy analysis of two stage refrigeration system and calculated the optimum COP value and optimum irreversibility values. Mohammad I. A. et. al. [21] performed energy and exergy analysis with R744 –R170 and calculated the optimum mass flow rate in terms of evaporator temperature, condenser temperature and cascade condenser temperature.

System Description

Fig. 1 shows the diagram of cascade refrigeration system and Fig. 2 , P-h diagram of cascade refrigeration system. This cascade refrigeration system contains two separate refrigeration system.

h (a) (b) Figure 1. Cascade vapour compression refrigeration system (a) Schematic (b) P-h diagram In this proposed system the temperature of evaporator in low temperature cycle is ranged between -70°C to -53°C, the temperature of condenser in high temperature cycle is ranged between -11°C to -2°C, and the temperature of evaporator in high temperature cycle is ranged between -19°C to -10°C. The entering refrigerant to the compressor for both low temperature and high temperature cycle are taken as saturated vapour.

Methodology

• In this analysis a set of equation for energy and exergy balance is prepared. • EES software is used to solve these equations • The result is compared by using different refrigerant pair for cascade refrigeration system.

Journal of Thermal Engineering, Technical Note, Vol. 6, No. 1, pp. 106-116, January, 2020

General Assumptions

• The system operates at steady state condition. • The kinetic and potential energy changes are negligible. • Pressure and heat loss in pipe network or system components are neglected. • The mechanical efficiency of each compressor is assumed to be 0.85. • The cooling demand of refrigeration system is 70kW. • The ambient temperature is 30°C.

Governing Equations For Mathematical Modeling

The mass, energy and exergy balance equation are applied for all the components in proposed system. Mass balance equation

where Q̇ is, heat transfer rate and 𝑊𝑊̇ is work transfer rate and h is specific enthalpy Exergy balance equation

where 𝐸𝐸̇𝑋𝑋 𝑖𝑖𝑖𝑖 and 𝐸𝐸̇𝑋𝑋 𝑜𝑜𝑜𝑜𝑜𝑜 are exergy rate at inlet and outlet of system respectively. 𝐸𝐸̇𝑋𝑋 𝐷𝐷 is exergy destruction rate. Exergy balance for control volume 𝑇𝑇 𝐸𝐸̇𝑋𝑋 𝐷𝐷 = Σ[(1 − 𝑇𝑇0 )𝑄𝑄̇]𝑜𝑜𝑜𝑜𝑜𝑜 − 𝑊𝑊̇ + Σ(𝑚𝑚̇𝑒𝑒)𝑖𝑖𝑖𝑖 − Σ(𝑚𝑚̇𝑒𝑒)𝑜𝑜𝑜𝑜𝑜𝑜

Specific equation for each components of cascade refrigeration system: For high temperature circuit: i) Compressor Mass balance:

where 𝑊𝑊̇𝐻𝐻𝐻𝐻𝐻𝐻 is work rate and 𝜂𝜂𝑚𝑚,𝐻𝐻𝐻𝐻𝐻𝐻 is mechanical efficiency of compressor of high temperature cycle. Exergy balance:

where (𝐸𝐸̇𝑋𝑋 𝐷𝐷 )𝐻𝐻𝐻𝐻𝐻𝐻,𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐 is exergy destruction rate of compressor of high temperature cycle. ii) Expansion valve Mass balance:

Journal of Thermal Engineering, Technical Note, Vol. 6, No. 1, pp. 106-116, January, 2020

where (𝐸𝐸̇𝑋𝑋 𝐷𝐷 )𝐻𝐻𝐻𝐻𝐶𝐶,𝑒𝑒𝑒𝑒𝑒𝑒 is the exergy destruction rate of expansion valve of high temperature cycle. iii) Condenser Mass balance:

where 𝑄𝑄̇𝐻𝐻𝐻𝐻𝐻𝐻,𝑐𝑐𝑐𝑐𝑐𝑐 is the heat rate of condenser of high temperature cycle. Exergy balance:

where (𝐸𝐸̇𝑋𝑋 𝐷𝐷 )𝐻𝐻𝐻𝐻𝐻𝐻,𝑐𝑐𝑐𝑐𝑐𝑐 is exergy destruction rate of condenser of high temperature cycle.

where 𝑄𝑄̇𝐿𝐿𝐿𝐿𝐿𝐿,𝑐𝑐𝑐𝑐𝑐𝑐 is heat rate of condenser of low temperature cycle. Exergy balance:

where (𝐸𝐸̇𝑋𝑋 𝐷𝐷 )𝐿𝐿𝐿𝐿𝐿𝐿,𝑐𝑐𝑐𝑐𝑐𝑐 is exergy destruction rate of condenser of low temperature cycle. For low temperature circuit v) Compressor Mass balance:

Journal of Thermal Engineering, Technical Note, Vol. 6, No. 1, pp. 106-116, January, 2020 Energy balance: 𝑚𝑚̇ (ℎ −ℎ ) 𝑊𝑊̇𝐿𝐿𝐿𝐿𝐿𝐿 = 1 2𝑠𝑠 1 𝜂𝜂𝑚𝑚,𝐿𝐿𝐿𝐿𝐿𝐿

where 𝑊𝑊̇𝐿𝐿𝐿𝐿𝐿𝐿 is work transfer rate of compressor of low temperature circuit. Exergy balance:

where (𝐸𝐸̇𝑋𝑋 𝐷𝐷 )𝐿𝐿𝐿𝐿𝐿𝐿,𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐 is exergy destruction rate of compressor of low temperature cycle. vi) Expansion valve Mass balance:

where (𝐸𝐸̇𝑋𝑋 𝐷𝐷 )𝐿𝐿𝐿𝐿𝐿𝐿,𝑒𝑒𝑒𝑒𝑒𝑒 is exergy destruction rate of expansion valve of low temperature cycle. vii) Evaporator Mass balance:

where 𝑄𝑄̇𝐿𝐿𝐿𝐿𝐿𝐿,𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑒 is heat transfer rate of evaporator of low temperature cycle. Exergy balance:

where (𝐸𝐸̇𝑋𝑋 𝐷𝐷 )𝐿𝐿𝐿𝐿𝐿𝐿,𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑒 is the exergy destruction rate of evaporator of low temperature cycle. The COP of high temperature cycle has been calculated by the following equations:

Journal of Thermal Engineering, Technical Note, Vol. 6, No. 1, pp. 106-116, January, 2020 The cascade system total COP is calculated by the following equation: 𝑄𝑄̇

Table 1. Thermodynamic and environmental properties of refrigerant used [4,5,23]

Results And Discussion

The effect of evaporator temperature, cascade condenser temperature and cascade evaporator temperature on actual COP, second law efficiency and total exergy loss has been calculated. In order to compare exergy performance of the system, different refrigerant pair has been used. Effect of parameters on total COP Fig. 2 and 3 shows the effect of evaporator temperature of LTC , evaporator temperature of HTC respectively on total COP of cascade refrigeration system for all the refrigerant pairs. It has been seen that the total COP is increasing at all the points and for all the refrigerant pairs with increase in evaporator temperature of LTC and the total COP is maximum for refrigerant pair R13-R717. Similar behavior is observed on total COP with increase in evaporator temperature of HTC. This is due to the reason that the value of 𝑄𝑄̇𝐻𝐻𝐻𝐻𝐻𝐻,𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑒 is maximum for refrigerant R717[21]. Because of high latent heat of vaporization, R717 will extract the more heat from cascade condenser and will produce more refrigeration effect. Fig. 4 shows the effect of condenser temperature of LTC on total COP. It can be seen from figure that with increase in condenser temperature, the COP is decreasing.

Journal of Thermal Engineering, Technical Note, Vol. 6, No. 1, pp. 106-116, January, 2020

-70 -68 -66 -64 -62 -60 -58 -56 -54 -53 Evaporator Temperature(LTC) (°C )

Figure 2. Variation of total COP with evaporator temperature (LTC) 1

-17 -16 -15 -14 -13 -12 -11 Evaporater Temperature (HTC) (°C )

Figure 3. Variation of total COP with evaporator temperature (HTC) R13 & R134a R13 & R290 R13 & R717

-11 -10 -9 -8 -7 -6 -5 -4 -3 Condenser Temperature (LTC) (°C )

Figure 4. Variation of total COP with condenser temperature (LTC) Effect of parameters on second law efficiency The effect of evaporator temperature of LTC on second law efficiency can be seen from figure 5.During the variation of evaporator temperature of LTC, other operating conditions were as follows : condenser temperature of HTC was 40°C, evaporator temperature of HTC was –15°C, condenser temperature of LTC was – 5°C. it can be seen from figure 5 that the second law efficiency is increasing with increase in evaporator temperature of LTC and it is maximum at all the points for refrigerant pair R13-R717 because, a higher evaporating temperature would lower the difference (ambient and cooling medium), so thermodynamically, it makes the system more efficient. Thus, the second law efficiency of the cascade system would increase due to increase in evaporator temperature. The similar effect can be seen in figure 6, in which second law efficiency is linearly increasing with increase in evaporator temperature of HTC.

Journal of Thermal Engineering, Technical Note, Vol. 6, No. 1, pp. 106-116, January, 2020

0,54 0,53 0,52 0,51 0,5 0,49 R13 & R134a R13 & R290 R13 & R717

Figure 5. Variation of second law efficiency with evaporator temperature (LTC) 0,56 Second Law Efficiency

-17 -16 -15 -14 -13 -12 -11 Evaporator Temperature(HTC)(°C )

Figure 6. Variation of second law efficiency with evaporator temperature (HTC) 0,59

Figure 7. Variation of second law efficiency with condenser temperature (LTC) Figure 7 shows the change in second law efficiency of cascade refrigeration system with respect to condenser temperature of LTC. In this figure evaporator temperature of LTC, evaporator temperature of HTC and condenser temperature of HTC are kept constant. It has been seen from the figure 8 that the second law efficiency is decreasing with increase in condenser temperature of LTC. In the considered temperature range, R13-R717 has the highest second law efficiency values while R13-R290 and R13-R134a have lowest one. Effect of parameters on total exergy loss The variation of total exergy loss with respect to evaporator temperature of LTC, evaporator temperature of HTC and condenser temperature of LTC has been shown in figure 8, 9 and 10 respectively. The total exergy loss of cascade system for all the considered refrigerant couple decrease when evaporator temperature of LTC

Journal of Thermal Engineering, Technical Note, Vol. 6, No. 1, pp. 106-116, January, 2020 increases. The similar effect has been seen in figure 9 with evaporator temperature of HTC. In the given set of conditions, R13-R717 has the minimum total exergy loss. As it was stated earlier, R13-R717 has maximum COP values, the increase of COP of cascade system decrease the power consumption, decrease the waste heat which thus, decrease the total exergy loss of cascade refrigeration system. It has been seen from figure 10 that the total exergy loss is increasing with increase in condenser temperature of LTC. 110

Figure 8. Variation of total exergy loss with evaporator temperature (LTC) 106

-17 -16 -15 -14 -13 -12 -11 Evaporater Temperature (HTC) (°C )

Figure 9. Variation of total exergy loss with evaporator temperature (HTC)

Figure 10. Variation of total exergy loss with condenser temperature (LTC)

Journal of Thermal Engineering, Technical Note, Vol. 6, No. 1, pp. 106-116, January, 2020

Conclusion

In this paper a novel two stage cascade refrigeration system has been proposed and the result has been compared using different refrigerant pairs. The effects of evaporator temperature of LTC, evaporator temperature of HTC and condenser temperature of LTC have been studied. The following are the conclusions resulted from this study: • Results show that, with decrease in evaporator temperature of LTC, the COP and second law efficiency of cascade system decreases whereas total exergy loss increases. The similar results have been found with decrease in evaporator temperature of HTC. • Results show that with increase in condenser temperature of LTC, the COP and second law efficiency decreases whereas total exergy loss increases. • In the considered all the refrigerant pairs, the cascade system was found most efficient with refrigerant pair R13-R717.

Nomenclature

Mass flow rate, kg/s ṁ h W E Q S COP Ƞ ȠII Ƞm o LTC HTC evap comp con cas ExD

Enthalpy, kJ/kg Work, kW Exergy Rate, kW Cooling Capacity, kW Entropy, kJ/kg-K Coefficient of Performance Efficiency Second law efficiency Mechanical Efficiency Atmospheric condition Low temperature cycle High temperature cycle Evaporator Compressor Condenser Cascade Exergy destruction

References

  1. G. Ehsan, H. Pedram, A. Pouria. Advance Exergy analysis of a Carbon Dioxide Ammonia Cascade Refrigeration Sytem. Applied Thermal Engineering 2018,DOI:https://doi.org/10.1016/j.applthermaleng.2018.03.055
  2. U. C. Rajmane. Cascade Refrigeration system: R404a-R23 Refrigerant. Asian Journal of Electrical Sciences, Vol. 6 (2017), pp. 18-22.
  3. F. A. Boyaghchi, S. Asgari. A comparative study on exergetic, exergoeconomic and exergoenvironmental assessments of two internal auto-cascade refrigeration cycles. Applied Thermal Engineering, 2017, pp. 723- 737.
  4. J.S. Jadhav, A.D. Apte. Review of Cascade Refrigeration System With Different Refrigerant pairs. International Journal of Innovations in Engineering Research & Technology, vol. 2 (2015), issue-6
  5. A. Mate, P. Panhale, V. Shinde, P. Mane, C.L. Prabhune. Design and Development of Cascade Refrigeration System. International Research Journal of Engineering and Technology, vol. 4(2017), pp. 1889-1891.
  6. S. Ponsankar, C. Balasuthagar, A.S. Kumar, M.I. Ahmed, M.D.K. Kaman. Performance and Irreversibility analysis of two stage cascade refrigeration system for different refrigerant pairs. Journal of chemical and Pharmaceutical Sciences, vol. 10 (2017), pp. 371-375.
  7. Nasruddin, Arnas, A. Faqih, N Giannetti. Thermoconomic Optimization of Cascade Refrigeration System Using Mixed Carbon Dioxide and Hydrocarbon at Low Temperature Circuit. Makara Journal of Technology, Vol. 20(2016), pp. 132-138.
  8. A. H. N. Khalifa, A. J. Hamad, H. S. Abdulhussein. Experimental Study on Auto Cascade Refrigeration Cycle Using Mixed Refrigerants R410A/R134a. Journal of Multidisciplinary Engineering Science and Technology, Vol. 3 (2016), pp. 5637-5641. 115 Journal of Thermal Engineering, Technical Note, Vol. 6, No. 1, pp. 106-116, January, 2020
  9. R. Karaali. Thermodynamic Analysis of a Cascade Refrigeration System. International Conference on Computational and Experimental Science and Engineering, Vol. 130 (2016), pp. 101- 106. DOI:
  10. R Selbas. An Application for Refrigerant Selecting In the Cascade Refrigeration Systems. Journal of YEKARUM, 2015. DOI: Yıl2015/Cilt3/Sayı1
  11. S. H. Mohammadi, M. Ameri. Energy and exergy analysis of a two-stage cascade refrigeration system. Building Service Engineering & Research Technology,2015. DOI:10.1177/0143624415615327.
  12. K.S. Rawat, R. Kshetri, H. Khulve, A.K. Pratihar. Parametric Study of R744- R717 Cascade Refrigeration System. International Journal For Research In Emerging Science And Technology, Vol. 2 (2015), pp. 101- 106.
  13. S.S. Seyitoglu, A. Kilicarslan. Second Law Analysis Of Different Refrigerants In A Two Stage Vapor Compression Cycle. Journal of Thermal Science and Technology, Vol. 2 (2015), pp. 89-97.
  14. A.D. Parekh, P.R. Tailor. Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290- R23 and R404A-R23. World Academy of Science, Engineering and Technology, International Journal of Mechanical and Mechatronics Engineering, Vol. 8 (2014), pp. 1351-1356.
  15. Y. Ust, A.S. Karakurt. Analysis of a Cascade Refrigeration System (CRS) by Using Different Refrigerant Couples Based on the Exergetic Performance Coefficient (EPC) Criterion. Arab Journal of Science & Engineering,2014,DOI 10.1007/s13369-014-1335-9.
  16. S. Tripathi, J. Jena, D.K. Padhiary, M.K. Roul. Thermodynamic Analysis of a Cascade Refrigeration System Based On Carbon Dioxide and Ammonia. International Journal of Engineering Research and Applications, Vol. 4 (2014), pp. 24-29.
  17. S.M.H. Mohammadi, M. Ameri, Energy and Exergy Comparison of a Cascade Air Conditioning System Using Different Cooling Strategies, International Journal of Refrigeration (2013), doi:
  18. 1016/j.ijrefrig.2013.06.015.
  19. B. Kilic, O. Ipek, S. Uguz. Evaluating On Exergy Analysis Of Refrigeration System With Two-Stage And Economiser. International Journal of Engineering & Applied Sciences, Vol. 4 (2012), pp. 15-25.
  20. A. Messineo. R744-R717 Cascade Refrigeration System: Performance Evaluation Compared With A HFC Two-Stage System. Energy Procedia 14 (2012), pp. 56-65.
  21. M.I. Alhamid, D.R.B. Syaka, Nasruddin. Exergy and Energy Analysis of a Cascade Refrigeration System Using R744+R170 for Low Temperature Applications. International Journal of Mechanical & Mechatronics Engineering, Vol. 10 (2010), pp. 1-8.
  22. M.B. Krikhan. Structures and Properties of Water. Principle of soil and plant water relations, Vol. 2 (2014), pp. 27-40.
  23. C. Kondou, F. Mishima, J. Liu, S. Koyama. Condensation and Evaporation of R134a, R1234ze(E) and R1234ze(Z) Flow in Horizontal Microfin Tubes at Higher Temperatures. International Refrigeration and Air Conditioning Conference , 2014, pp. 1446. DOI: http://docs.lib.purdue.edu/iracc/1446. 116

Share and Cite

Kumar, V.; Karimi, M.N.; Kamboj, S.K. Comparative analysis of cascade refrigeration system based on energy and exergy using different refr. Journal of Thermal Engineering 2020, Vol. 6, pp. 106-116. https://doi.org/10.18186/thermal.671652

Export:

Related Articles

Optimum parametric analysis based on thermodynamic modeling of a compression absorption cascade refrNaushad Ahmad Ansari, Akhilesh Arora et al., 1 January 2020Optimization of the variable refrigerant flow systems by use of genetic algorithm and energy exergyM. Lotfihejrandoost, A. Behbahani et al., 1 January 2020Thermal design and CFD simulation of an internal heat exchanger with R1234yf as an alternate refrigeB. K. PATEL, A D. PAREKH, 1 January 2025Comparative evaluation of experimental ejector refrigeration system for different operating configurBatuhan ÜĞÜDÜR, Mehmet DİREK, 1 January 2024
Publication History
Published1 January 2020
Versionv1
AccessOpen Access
10.18186/thermal.671652
Article Figures (1)
Figure 1
Related Articles
Optimum parametric analysis based on thermodynamic modeling of a compression absorption cascade refrNaushad Ahmad Ansari, Akhilesh Arora et al.Journal of Thermal Engineering, 1 January 2020Optimization of the variable refrigerant flow systems by use of genetic algorithm and energy exergyM. Lotfihejrandoost, A. Behbahani et al.Journal of Thermal Engineering, 1 January 2020Thermal design and CFD simulation of an internal heat exchanger with R1234yf as an alternate refrigeB. K. PATEL, A D. PAREKHJournal of Thermal Engineering, 1 January 2025
Journal of Thermal Engineering coverJournal of Thermal Engineering Download PDF

Subscribe to YTUP

Stay connected and receive the latest research updates directly in your inbox.

YTUP — Yıldız Technical University Publishing

Advancing knowledge and fostering innovation through high-quality, peer-reviewed academic publications.

About YTU

Discover

  • ›Articles
  • ›Journals
  • ›Research Topics
  • ›Open Access Policy

Guidelines

  • ›Author guidelines
  • ›Services for authors
  • ›Policies and publication ethics
  • ›Editor guidelines
  • ›Fee policy

Explore

  • ›Articles
  • ›Research Topics
  • ›Journals
  • ›How we publish

Support

  • ›Help center
  • ›Emails and alerts
  • ›Contact us
  • ›Submit
  • ›Career opportunities
YTU Logo

© 2026 Yıldız Technical University (Istanbul, Turkey)

Terms and ConditionsTerms of UsePrivacy PolicyPrivacy SettingsDisclaimer
Like this platform? Join our teamHave feedback or questions?
Supervisor